Helinks STS 2021-07 V 3.4.0 Quarterly Release Release Note


https://arn-resources.upraise.io/images/cloudARN_3224947a-1e01-49b5-8031-1674a7b148d5.png

Release Date: 30.06.2021


Helinks STS 2021-07 V 3.4.0 Quarterly Release is now available for download in the Helinks Customer Portal: Helinks Customer Portal


What is New?

Library improvements

Improved IEC 60870-5-104 support

UI Improvements

Improved ProxyCrafter

Improvements and Bugfixes to Process Editor
Various Bugfixes




Detailed Feature and Change Description


Library improvements


  • Copy & Paste of Library elements in the Library Manager will now copy the backing files

  • Bay templates now correctly store the orientation of conducting equipment

  • Function and IED library elements can now be used in bus bar specification diagrams

  • Handling of logical node instance number calculation improved


Improved IEC 60870-5-104 support


  • Exposed CAA attribute in the default signal table

  • DAI creation no longer fails for specific data attributes


UI Improvements


  • Support for adding and removing logical node data instance values (DAI)

  • Support for data specification values (DAS)

  • Rotating unconnected power equipment takes effect immediately, not after deselection

  • Bay specification diagram is now closed if the bay is deleted in the single line diagram

  • Sampled value AppId was incorrectly labeled as SMV ID (in addition to the actual SMV ID)

  • Templated application groups can now override MAC addresses and AppIDs for GOOSE and SMV on a per-checkmark base

  • Editing the “Template” field of Functions and Conducting Equipment will now present a drop-down menu of existing library keys, in addition to free text editing

  • MMS Subscription (client-side initiated) now allows to choose the specific Report Application + Configuration where signal connections are created


Improved ProxyCrafter


  • Supports creation of a Proxy IED based on existing Reports, GOOSE or SMV

  • Support for incremental crafting / merging into existing IEDs


Improvements and Bugfixes to Process Editor


  • added support to create and assign virtual IEDs

  • MMS Clients can now be configured entirely within the Process Editor

  • Logical node mapping dialog can now properly display and handle process hierarchies





The following Bugs are fixed in this Version

Priority

Key

Summary

Status

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-1006

Instantiate Bay dialog shows SubFunctions/SubEquipment in the list of optional functions

Done

https://helinks.atlassian.net/images/icons/priorities/highest.png

STS-1005

PowerEquipment function not represented in MMS Report Input

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-1004

Importing with default.pio does not resolve Conducting Equipments

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-1003

Excel export did not properly resolve 'IEC 61850 Specified' column

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-1002

Application Template Connection Matrix may erroneously declare "Sending & Receiving"

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-996

Excel import does not match existing specified LNodes with implemented imported

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-995

Excel import with default.pio does not correctly resolve data references

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-993

ApplicationRole configuration automatically includes candidates in mapping

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-991

TVoltageLevel does not properly set multiplier

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-990

New name calculation may cause collision if proposed name ends in digit

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-989

DAI lookup fails if similarly named DAI exists

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-988

104 Address bay-wise calculation is disabled

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-985

Pasting LLN0 does not correctly pickup inst collisions with existing LLN0

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-984

Pasting LNode into SCL Functions does not correctly disambiguate inst

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-983

Touching LLN0 'inst' field forces non-empty prefix

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-982

LNode specified prefix may be overwritten by implementation prefix

Done

https://helinks.atlassian.net/images/icons/priorities/high.png

STS-973

Instantiate IED in BusBar does not instantiate related Functions

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-966

Pasting ConductingEquipment "steals" Functions from original ConductingEquipment

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-964

IEDCrafter: calculate new data types checkbox not functional

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-963

Synchronizing EMF resource

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-962

Preserve Instance numbers from library when instantiating Conducting Equipment

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-957

Referencing non-existent data in notation file causes unresolvable crash of GMF editors

Done

https://helinks.atlassian.net/images/icons/priorities/high.png

STS-955

ComConf does not handle dataset overflow for indexed connections

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-943

Copy Paste in Library Manager does not copy Library File

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-937

Library instantiation creates default Power Equipment Functions

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-927

IEDCrafter sets LdName of new TLDevices by default

Backlog

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-922

erroneous LNode Inst disambiguation

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-904

Projects without Substations can not export SCD

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-835

Equipment orientation is lost on bay template instantiation

Done

https://helinks.atlassian.net/images/icons/priorities/lowest.png

STS-675

STS nature project not referenced

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-595

Copy & Paste of Applications erroneously uses shared SinkItems

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-584

Set voltage value properly when importing SSD File

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-581

Instantiating LNType does not copy private fields from sclns to DataTypeTemplates

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-514

Map LNodes should show hierarchy segments for functions in Process Editor

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-513

Map Specification to IED pane in mapping dialog doesn't properly resolve nested Process elements

Done

https://helinks.atlassian.net/images/icons/priorities/medium.png

STS-229

Drag'n'Drop of Logical Nodes does not trigger uniqueness maintaining instance number change from edit provider

Done



Looking forward to hear your feedback.