Skip to main content
Skip table of contents

Helinks STS 2021-10 V 3.5.0 Quarterly Release Release Note

 

Helink sLogo

Release Date: 30.09.2021


Helinks STS  2021-10 V 3.5.0 Quarterly Release is now available for download in the Helinks Customer Portal: Helinks Customer Portal


Detailed Feature and Change Description

Improved SCL Validation

Various improvements for SCL validation and conversion

Library improvements

  • Copy & Paste of Library elements in the Library Manager will now copy the backing files
  • Bay templates now correctly store the orientation of conducting equipment
  • Function and IED library elements can now be used in bus bar specification diagrams
  • Handling of logical node instance number calculation improved

Improved IEC 60870-5-104 support

  • Exposed CAA attribute in the default signal table
  • DAI creation no longer fails for specific data attributes

UI Improvements

  • Support for adding and removing logical node data instance values (DAI)
  • Support for data specification values (DAS)
  • Rotating unconnected power equipment takes effect immediately, not after deselection
  • Bay specification diagram is now closed if the bay is deleted in the single line diagram
  • Sampled value AppId was incorrectly labeled as SMV ID (in addition to the actual SMV ID)
  • Templated application groups can now override MAC addresses and AppIDs for GOOSE and SMV on a per-checkmark base
  • Editing the “Template” field of Functions and Conducting Equipment will now present a drop-down menu of existing library keys, in addition to free text editing
  • MMS Subscription (client-side initiated) now allows to choose the specific Report Application + Configuration where signal connections are created

 

The following Bugs are fixed in this Version

PriorityKeySummaryStatus

Medium

STS-1006

Instantiate Bay dialog shows SubFunctions/SubEquipment in the list of optional functions

Done

Medium

STS-1004

Importing with default.pio does not resolve Conducting Equipments

Done

Medium

STS-1003

Excel export did not properly resolve 'IEC 61850 Specified' column

Done

Medium

STS-1002

Application Template Connection Matrix may erroneously declare "Sending & Receiving"

Done

Medium

STS-996

Excel import does not match existing specified LNodes with implemented imported

Done

Medium

STS-993

ApplicationRole configuration automatically includes candidates in mapping

Done

Medium

STS-991

TVoltageLevel does not properly set multiplier

Done

Medium

STS-990

New name calculation may cause collision if proposed name ends in digit

Done

Medium

STS-988

104 Address bay-wise calculation is disabled

Done

Medium

STS-985

Pasting LLN0 does not correctly pickup inst collisions with existing LLN0

Done

Medium

STS-984

Pasting LNode into SCL Functions does not correctly disambiguate inst

Done

Medium

STS-983

Touching LLN0 'inst' field forces non-empty prefix

Done

Medium

STS-982

LNode specified prefix may be overwritten by implementation prefix

Done

High

STS-973

Instantiate IED in BusBar does not instantiate related Functions

Done

High

STS-955

ComConf does not handle dataset overflow for indexed connections

Done

Medium

STS-943

Copy Paste in Library Manager does not copy Library File

Done

Medium

STS-937

Library instantiation creates default Power Equipment Functions

Done

Medium

STS-835

Equipment orientation is lost on bay template instantiation

Done

Medium

STS-595

Copy & Paste of Applications erroneously uses shared SinkItems

Done

Medium

STS-581

Instantiating LNType does not copy private fields from sclns to DataTypeTemplates

Done

Medium

STS-229

Drag'n'Drop of Logical Nodes does not trigger uniqueness maintaining instance number change from edit provider

Done

Looking forward to hear your feedback.

 

Thanks,

Team Helinks STS

JavaScript errors detected