Skip to main content
Skip table of contents

Helinks STS STS-2023-04 V3.9.0 Semi Annual Release Release Note

 

Helink sLogo

Release Date: 01.04.2023


Helinks STS  STS-2023-04 V3.9.0 Semi Annual Release is now available for download in the Helinks Customer Portal: Helinks Customer Portal


Detailed Feature and Change Description

Document Generation


  • Add SMV tables to SCD section of PDF document

Improvements in IEC104 address calculation


  • Allow Bay and Busbars individually of combined as address qualifiers
  • Allow IED Role as address qualifier

Improved Signal Engineering Dialogs


  • Faster creation of MMS Inputs
  • Prevent wrong error messages
  • Improved Result Log for Flexible Naming
  • Fixes for unique names
  • Improved variable support
  • Formula support for mapping variants
  • Formula support for Assigned Device name
  • Save Layout of Function Diagram in Library

Imroved Reverse Engineering

Better Support to extract th eSignal List form an imported SCD file

Improvements and fixes for IED elements in the Library


  • Ensure assigned Functions are also in the Library
  • Fix instantiation of IEDs problem

Vendor Package improvements


  • GE Vendor Package
  • ABB/Hitachi vendor package

Various bug fixes and imrovements for the Communication Configuration (Control Blocks and Datasets)


  • Proper updating ConfRev
  • Proper handling of multiple dataset overflows
  • Improved result log of the ComConf execution
  • Fix for SMV Mac address setting
  • Fix for LSVS settings

Fixes and Improvements for Excel Import Export


  • If more than one version of STS is installed on computer there may be a mix up of ptd and pio file. This results in problems with the Signal List and the Excel Import Export. This is fixed by managing dedicated ptd and pio files for each installed software instance.
  • Improved Import Log
  • Fix for false LNode Resolving when identical LNodes are in different Logical Divices.

 

The following Bugs are fixed in this Version

PriorityKeySummaryStatus
MediumSTS-1272Initializing Report Signal Connections from a FCDA with no dA leads to FCDA.dA being set Done
MediumSTS-1270If ComConf creates a Dataset and the ConfigRev of the ControlBlock is 0 it should be incremented even if th eData Set is identical to the existing one .Done
MediumSTS-1268New UR devices allow Data Sets with more than 64 entries despite different Service Section. Done
MediumSTS-1267Virtual IED instantiation from Library failsDone
MediumSTS-1265Default SMV MAC is wrongly set from GOOSE MAC Done
HighSTS-1264AssignedDevice deviceRole should be forced to be unique within Function diagramDone
HighestSTS-1263Do not create a dangling report link for all imported report signals during excel importDone
LowSTS-1251SCL Communication Configuration log shows wrong hierarchy in "Analyzing specification"Done
MediumSTS-1247Opening SIL or SSF diagram can lead to 'Semantic refresh failed' errorDone
MediumSTS-1238Long digit suffixes in elements crash calculation for unique namesDone
MediumSTS-1237Existing control blocks are not properly reset during SCL configuration synchronizationDone
MediumSTS-1234Formula Editor for Function Configuration loses value.Done
MediumSTS-1233Variable is not resolved for Function AttributesDone
MediumSTS-1231Bay or Bus Bar object reference for 104 Address calculation is not workingDone
MediumSTS-1230Extended Parameter referencing Variables of Substation are not resolvedDone
MediumSTS-1229Extended Parameter referencing Variable of Equipment Functions are not resolvedDone
HighSTS-1227Report Application Channel selection dialog does not show any report channelsDone

Looking forward to hear your feedback.

 

Thanks,

Team Helinks STS

JavaScript errors detected

Please note, these errors can depend on your browser setup.