Helinks STS 2020-10 V.3.1.0 Quarterly Release Release Note


Helink sLogo

Release Date: 01.10.2020


Helinks STS 2020-10 V.3.1.0 Quarterly Release is now available for download in the Helinks Customer Portal: Helinks Customer Portal





Detailed Feature and Change Description

Communication Configuration


  1. Improved Logging with hierarchical log representation
  2. Improved Invocation Dialog
  3. Flexible Support for APPI and MAC Address calculation
  4. Driven entirely by channel configuration
  5. Support for SCL Ed 2.1 service section
  6. Improved LGOS and LSVS Support
  7. Later Binding Support
  8. Communication Configuration Differences Editor with GOOSE and SMV support


Signal List


  1. Sorting and Filtering
  2. Performance improvement
  3. Flexible Excel loading
  4. IEC 60870-5-104 Address calculation
  5. DNP 3 Address calculation (option)


Communication Editor


  1. Sampled Value communication Matrix
  2. LGOS and LSBVS tabs
  3. Process tab shows the SCL Process/Substation section
  4. Improved performance


Process Editor


Support for IEC 61850 process elements. The Process Editor allows IEC 61850 modelling of non Substation electrical systems, e.g. DER, Hydro Power Plants, or Wind Turbines.


Application Editor


  1. Support for Client Server Applications
  2. Improved Channel configuration
  3. Sample Value Application Editor added
  4. Line colouring fo channel indication
  5. Improved connection layout with welding points


Function Diagram Editor


Support for multiple Power Equipment Functions

Improved Auto Layout

Improved Logical Node Mapping Dialog

  • Bidirectional Mapping
  • Automapping creates Mapping suggestions based on LNode matching score

Function Configuration Dialog

  • Inclusion of Functions in SCL is configurable
  • Support for Subfunctions, Equipment Functions and Subequipment Functions
  • Support for SSCL Sub Equipment
  • Support for SCL Power System Resource References

IED Crafter

  • Flexible Naming
  • Lxxx Nodes from customizable Namespace
  • Support for custom Logical Device structure


Library Support


  1. Power Equipment Library with intrinsic Functions
  2. Improved adding and instantiating process
  3. GOOSE and SMV Application Templates
  4. Nested Functions support


Excel Import and Export


  1. Support for custom mapping files
  2. Flexible import process with free column mapping and string matching


SCL Import and Export


  1. Auto recognition of SCL File Type
  2. Improved merging of Subnets
  3. Improved merging of Data Types
  4. CID import with suppression of Publishers
  5. CID file export with optionally included Publishers


IEC 61850 SCL


  1. Support for TF IEC 61850 6- 100 Function Modelling
  2. Support of SCL schema version 2007 B4


IED Life Cycle


  1. Icons close to the IEDs in the System Diagram indicate the status of the IED: Configured,Modified, Locked


Workbench and Runtime


  1. 64 Bit support allowing for larger projects without memory shortage (>100 IEDs)
  2. Usage of to Open JDK
  3. Facilitate project exchange by Import and Export of Projects from Project menu





The following Bugs are fixed in this Version

PriorityKeySummaryStatus
MediumSTS-659ComConf overrides CB Block parameters unless resettingDone
MediumSTS-658ReportLinks and their Inputs do not consistently get deletedDone
MediumSTS-657Deleting SignalConnection in SCLApplicationView may cause project corruptionDone
MediumSTS-656SubstationLevels do not properly clean up ReportSignalConnectionsDone
MediumSTS-653Duplicate Logical Node breaks TLNode linkDone
MediumSTS-652ComConf vault/generation does not handle AppID '0000' properlyDone
MediumSTS-650SMV Application initial default settings changed to conform to IEC 61850-9-2LEDone
MediumSTS-649DPF: selecting LNode as SignalConnection end point should never reuse existing SinksDone
MediumSTS-643DPF SignalSelection returns signal in random orderingDone
MediumSTS-642Ed2 LLN0 has wrong Oper definitionDone
MediumSTS-641SCLApplicationView does not initialize empty TemplatedApplicationGroup details properlyDone
MediumSTS-639Adding Bay to library does not properly update elements with duplicate keyDone
MediumSTS-638STSLibraryManager allows library index delete without corresponding UI updateDone
MediumSTS-637STSLibraryManager has unwanted popup menu entriesDone
MediumSTS-634Library import does not check for valid library before unzippingDone
MediumSTS-633DataSet Overflow causes new DataSet to exceed FCD(A) limit by 1Done
MediumSTS-632DataSet Overflow causes extra DataSet with only 1 FCD(A) being createdDone
MediumSTS-631AddEquipmentToLibrary can be used on multiple selections, but only works for first elementDone
MediumSTS-629Importing CID files should not by default import all IEDs, only the firstDone
MediumSTS-628ComConfDifferences Editor does not properly diff GOOSE, SMV, ExtRefDone
MediumSTS-627ComConf does not log error if no suitable location for TGSE/TSMV is foundDone
MediumSTS-619ComConf with "Reset ConfRevs" may still trigger auto-increment, deviating from initial value from channelDone
MediumSTS-618confRev no longer auto-increments on dataset changesDone
MediumSTS-611Goose Matrix improperly calculates subscriptionsDone
MediumSTS-610Configuration of MAC address & AppId should be handled by dialog, not preferences Done
MediumSTS-608SourceRefUtil tries to update SourceRef for removed SignalItems, causing logged errorsDone
HighSTS-604DAI elements are not properly created for Structured Data AttributesDone
MediumSTS-587Favor Warnings and Errors over Info when log overflow occurs.Done
MediumSTS-583Later binding ExtRef key no longer contains IED name to improve reusabilityDone
MediumSTS-574SCD generation preference does not properly store or retrieve SV Sampling modeDone
MediumSTS-573Instatiating domain elements via diagram does not add ItemProvider adapters unless Property view is openDone
MediumSTS-572Importing SCD file no longer connects all new devices to same subnetworkDone
MediumSTS-571C30 Pixit should inherit from URPixitDone
LowSTS-570Deleting all FCDAs in a a data set at once now worksDone
HighSTS-561Stored prefixes of implemented LNodes are no longer overwritten if prefix is emptyDone
MediumSTS-558Zenon Excel export reports error even when successfully completedDone
MediumSTS-548Function Library instantiation breaks foreign LNode signal mappingDone
MediumSTS-547IEDSynchronisationStatus changes model when building connection treeDone
MediumSTS-544Variants now support SignalItem mappingDone
MediumSTS-538IEC 104 addresses not properly created for Pos.Oper.ctlValDone
HighSTS-534LNode mapping of main implementation takes priority over variantDone
MediumSTS-521Indexed Reporting configuration creates errorDone
MediumSTS-511SCD Export updates filename to project version/revision only if configuration detail dialog is openedDone
MediumSTS-510SCD Export updates changes to export file name only when external folder is setDone
LowSTS-419Remove "Application Editor" Icon from Top Level ToolbarDone
MediumSTS-418Power Transformer Winding connection problem in Single LineDone
MediumSTS-417Excel import does not resolve LNType from non-standard namespacesDone
MediumSTS-261Namespace editor save causes Invalid Thread access ExceptionDone
MediumSTS-183Create ICD from Specification dialog ICD Template field is initialized with IED Type valueDone
MediumSTS-181Create IED From Specification dialog does not respect Cancel buttonDone
MediumSTS-178Copy & Paste of Applications does create name conflictDone


Looking forward to hear your feedback.


Thanks,

Team Helinks STS