Skip to main content
Skip table of contents

Helinks STS V3.12.4 release notes

Date

Version

3.12.4

Description

Maintenance release

Improvements to existing features

  • IEDs with fixed control blocks: If a service configuration of an application can not find any control block with compatible parameters, the reason for rejecting a control block will be logged

Bug fixes

  • Predefined report control blocks with configured ‘max’ were automatically decremented when a client was removed.

  • After an IED with freely configurable control blocks is replaced with an IED with fixed control blocks, the applications still contained stale data that would erroneously recreate the freely configurable control blocks.

  • Single Line and Function Diagram palettes did not correctly update when relevant library elements were added or removed

  • ICD file names with characters such as spaces were stored in a format unsuitable for reopening the file

JavaScript errors detected