Demo Berlin
use the attached resources :
library
start project
Berlin_Demo_Library_V1R000_YT.zip Berlin_Demo_Project.zip
Introduction
Present people and participants
Give a short Introduction on Helinks and on the Engineering Process (Slides)
Demo
Introduction
Present Dashboard Icons
Single Line Editor for the specification
Process editor: 61850 specification of general electrical systems
Application Editor for data exchange
Namespace editor allows users to create their own namespaces
Import to import any kind of SCL file + Excel files
System diagram to represent the network and the IEDs of the project and the AccessPoints
Export the produced SCL files
Communication represent the actual SCL projet over multiple visualisation axes.
Quickly introduce the start state of the project (partially done)
System Diagram (only E03BPU is messing to show the work step with the System Diagram)
Usage of predefined library
Application already present but empty with automatization of the process.
SampledMeasurments : where the PIU send SV to protection and to Control for MMXU
Switch and Breaker control : where the PIU send the position to the control and the control send the commande to the PIU
Trip : where the protection send trip to the PIU
Breaker failure : the most complex one with more participant
the PIU activate the breakerfailure of the controler
the Controler do the internal Breakerfailure to the PIU breaker interface
the Controler do the external BreakerFailure to the PIU breaker interface of the transfo
=> but no signals and/or input define this will come with the instantiation of the bay from the library.
Show the content of an application
Single line
show HMI and SCADA
=> but no signals and/or input define this will come with the instantiation of the bay from the library.
Show the state of the SCL project before we start : no dataset.
Show the content of the library.
Start the specification of the substation base on the library.
Single Line Editor
Instantiate the bays from the library.
01 line
show the content of the instantiation
signal list
inputs
Show the application
02 transformer
03 line
04 line
05 transformer
06 line
Do Electrical connection
Now we have done the Specification of the substation !
then we need to assign the physical IED to the Virtual device roles in the bay and map the specification LN and Signals to the relay information.
Show automatic implementation of the IEDs
explain the how the mapping is retrieve from the library (use PDIS in on bay and show IED type mappign)
Explain Signal List with mappings and IED Type Mappings
Explain why one IED isn’t implemented
Show System Diagram
add the missing ABB IED
Do manual implementation for the new added IED
Show Communication Editor content
Now the mapping is done we can then generate the communication. The generated communication will take in account the specification, the mapping to the IEDs, the service section of the IEDs and the Manufacturer know specificities.
Create SCL Configuration
see the configuration on E01BCU
Show Result in Communication Editor
dataset no more empty
show report BUP with predefined
show goose matrix…
Export SCD
Show GOOSE Inputs in SCD with xml editor
Run and Show Documentation
Explain the normal workflow vs the demo.
library definition
Single line
Application Editor
Export SSD and documentation
Import icd
System diagram
Implementation
communication configuration
Export SCD and documentation